Control Module Configuration
22
Banner Engineering Corp. • Minneapolis, U.S.A.
Website:http://www.baneng.com • Tel:888.373.6767
4.7 Output Configuration (Analysis Mode Assignment)
Bothoutputs#1and#2(“Alarm”)individuallymaybeassignedtooneoftheScan
AnalysisModesselectedforMeas 1orMeas 2ortheymaybeDisabled.Eitheroutput
maybedisabled,butnotbothatthesametime.
EachoutputhasLowandHigh Set Pointoptions.Thenumberselectedforeach
optionidentifiesabeaminthearray(beam#1beingclosesttothecabledendofthe
emitterandthereceiver).WhentheselectedScanAnalysisModeinvolvesfirstorlast
beamblockedormade(unblocked),theassignedoutputwillenergizewhenthebeam
identifiedduringascanfallswithintherangeofthesetpoints.WhentheScan
AnalysisModeinvolvestotalbeamsblockedormade,thatassignedoutputwill
energizewhenthevalueoftotalbeamscountedduringascanfallswithintherangeof
thesetpoints.
Invert isanoption(chooseYesorNo)thatmaybeappliedtoeitherorbothofthe
selectedoutputs.WhenInverted (Yes) isselectedforanoutput,thatoutputwill
de-energize(turnOFF),ratherthanenergize,wheneverthescananalysisvaluefalls
withintherangeofthesetpoints.
Hysteresisvaluesforeachendofthesetpointrangemayalsobeset.Hysteresis
determinestheamountofchangethatmustoccurateachsetpoint(HighandLow)
tocausetheassociatedoutputtochangestate.Hysteresispreventsunstableoutput
conditionswhenthescananalysisvalueexactlymatchesoneofthesetpoints.The
defaulthysteresissettingisonebeamlessthantheLowSetPointandonebeam
morethantheHighSetPoint.
Alarm and Trigger
Output#2(only)hastwoadditionaloptions:AlarmandTrigger.
Alarm:Output#2energizeswhenevertheSystemdetectsasensorerror(suchasa
disconnectedcable).
Trigger: canbeusedtogateasecondcontrolmodule.TheTriggeroutputisa100
microsecond(0.0001sec.)pulse.Ifthecontrolmoduleissetforedgescan,the
Triggerpulsewillcomeattheendofthescan(Trigger Channel Numberwillbe
ignored).