Banner A-GAGE High-Resolution MINI-ARRAY Series Manual de usuario Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 40
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
29
Banner Engineering Corp. •Minneapolis,U.S.A.
www.bannerengineering.com•Tel:763.544.3164
P/N64118rev.B
5.4 Serial Communication with a Host Controller
ThecontrolmodulecommunicateswithahostprocesscontrollerviaRS-232or
RS-485protocolandatthebaudratespecifiedintheSerialCommunicationsbox
(section5.3.1).TheSystemprovidesanumberofdatatransmissionoptions.
5.4.1 Serial Data Transmission
TheserialtransmissionportionofthePSFConfigurationscreenactivatestheserial
port(s),specifiesthedataformat,andprovidesdatasuppressionoptions.These
settingsarerequiredtoallowacontrolmoduletocommunicatewithahostcomputer
orprocesscontroller.IfNo Serial Communicationisselected(thedefaultsetting),
theserialport(s)willnottransmitsensingdata.
Measurement Mode Result: datatransmittedwillbethevaluesoutputfortheScan
AnalysisModeselections.UptotwoScanAnalysisModeselectionscanbeactive.
ALL Mode: thestatusofeachbeaminthelightscreenarraywillbetransmittedfor
each scan. InALLmode,blankedchannelsaretransmittedasunblocked(orclear)
beams.
Max Meas Mode: thecontrolmodulerecordsthemaximummeasurementvalue
registeredwhilethelightscreenisblocked.Thatdatamaybetransmittedtothehost
eitherwhenthearrayisclearattheendofthesensingevent(selectSend On Clear),
orwhenpromptedbythehost(selectSend On Request).Thismodereducesthe
amountofserialdatasent.
5.4.2 Transmission Type
Transmissiontypedefinestheformatinwhichdataissent.TheASCIIoptioncauses
thecontrolmoduletosenddatainthreeASCII-codedbytes.TheBinaryoptioncauses
datatobesentinbinaryformat,reducingtheamountofdatapermeasurementmode
fromthreebytestotwo.Formoreinformationonthedataformats,refertoAppendix
A.
Figure 5-25. Serial Data Transmission
options (PSF Configuration
screen)
Control Module Configuration
Banner Engineering Corp. •Minneapolis,U.S.A.
www.bannerengineering.com•Tel:763.544.3164
Vista de pagina 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 39 40

Comentarios a estos manuales

Sin comentarios